2-12 Netra CP32x0 SAS Storage Advanced Rear Transition Module HD User’s Guide January 2009
2.6 Changing the OOS LED Color
The color of the Out-of-service (OOS) LED can be set to red or amber by moving
jumper JU1 to the appropriate position. Setting the jumper to the P1/P2 position
makes the OOS LED appear red. Setting the jumper to the P2/P3 position makes the
OOS LED appear amber. Amber (position P2/P3) is the default setting for the OOS
LED.
1. Remove the ARTM-HD from the chassis.
See Section 2.3, “Removing the ARTM-HD” on page 2-9.
2. Locate jumper JU1 on the board.
JU1 is located next to the Primary SAS connector.
FIGURE 2-6 Jumper setting for red OOS LED (P1/P2)
3. Set the jumper housing to the appropriate setting; P1/P2 for red, P2/P3 for
amber.
Jumper 1